CHAPTER 4:
4.1
Parallel Operation
RFE1600
+V
+SENSE
J1-2
-SENSE
J1-1
-V
ENABLE
J1-8
SIGNAL RETURN J1-17
V_PROG
J1-3
TRIM J1-12
CURRENT SHARE J1-16
RFE1600
+V
+SENSE
J1-2
-SENSE
J1-1
-V
ENABLE
J1-8
SIGNAL RETURN J1-17
V_PROG
J1-3
CURRENT SHARE J1-16
RFE1600
+V
+SENSE
J1-2
-SENSE
J1-1
-V
ENABLE
J1-8
SIGNAL RETURN J1-17
V_PROG
J1-3
CURRENT SHARE J1-16
POWER SUPPLIES CONNECTION
Figure 4–1:
LOAD
+V
-V
•
Up to 10 x RFE1600 units with the same rating (voltage
and current) can be used in parallel to increase the output
current.
•
By connecting the CS signal between the paralleled units,
automatic current balance is achieved with accuracy of
Accuracy ±10%:
Accuracy ±5%:
•
Derate the total output current by 5% when using parallel
operation to prevent unit overload condition.
The built-in O-Ring MOSFETs on the main output and the
•
12V Auxiliary output allow N+1 operation.
•
If Voltage programming is used, "V_PROG" inputs of all
units must be connected in parallel.
•
Referenced to "SIGNAL RETURN" (floating from the
output) controls/signals and +12V AUX can be connected
in parallel.
•
ENABLE of all supplies can be connected to a single
switch.
For PMBus option.
•
If voltage programming is done with PMBus, Voltage
Programming and V_REF of all units must be connected in
parallel.
Connect PMBus Signals in parallel (PMBUS is isolated from
•
output), and choose different address for each unit.
•
If Current Programming is done with PMBUS, Current
Programming and V_REF of all units must be connected
in parallel.
Parallel Connection
16
20% ≤ Iout < 50% of max Iout.
Up to 10 units
Iout ≥ 50% of max Iout.
Up to 10 units.