3.2
Single unit operation
3.2.1
Basic configuration (Local Sense)
•
± SENSE have to be connected to the RFE1600 ± Local SENSE terminals prior to operating the supply.
ENABLE input must be connected to SIGNAL RETURN in order for the supply to turn on.
•
3.2.2
Basic configuration (Remote Sense)
± SENSE have to be connected to the ±V terminals on the Load side prior to operating the supply.
•
ENABLE input must be connected to SIGNAL RETURN in order for the supply to turn on.
•
1. Maximum voltage drop on load connection:
RFE1600-12: 0.25V/wire; RFE1600-24: 0.5V/wire; RFE1600-32: 0.75V/wire; RFE1600-48: 1V/wire.
2. Twisted wires should be used for Remote Sensing connection.
3. If Remote Sensing is used, do not break Main Output connection.
Figure 3–2: Local Sense Connection
Figure 3–3: Remote Sense Connection
ATTENTION: