3.2.8
Over Current Programming by External Voltage
Over Current Protection (OCP) can be programmed by external voltage source 0~5V. By changing the Current
Programming Voltage OCP level could be decreased down to ~40% of Nominal Output Current.
3.2.9
SUPERVISORY Signals (Typical Connection)
The following supervisory signals are accessible:
DC OK
•
•
AC FAIL
•
PS EXIST
•
TEMP ALARM
SIGNAL RETURN and mentioned signals are isolated from the output terminals and -SENSE.
These signals are Open Collector type (max 15V, max 10mA) shunted by internal 24V Zener, isolated from Output and
referenced to "SIGNAL RETURN".
Figure 3–14:
RFE1600
CURRENT PROG.
-SENSE
Figure 3–11:
Current Programming by Ext. Voltage
Icl / Irated
Current Limit Programming
120%
100%
80%
60%
40%
20%
0
0
1
2
Figure 3–12:
Current Limit Programming
RFE1600
+12V AUX
J1-18
10kΩ
10kΩ
DC OK
J1-7
AC FAIL
J1-15
TEMP ALARM
J1-6
SIGNAL RETURN J1-9
Figure 3–13:
Open collector signals are shunted by internal 24V Zener
J1-4
+
0~5V
J1-1
4
3
5
V PROG [V]
10kΩ
Signals
15