Herunterladen Inhalt Inhalt Diese Seite drucken

On/Off Control By Enable; Output Voltage Programming By Built-In Potentiometer; Output Voltage Programming By Pmbus (Optional) - Tdk-Lambda Rfe1600 Serie Bedienungsanleitung

Inhaltsverzeichnis
3.2.3

ON/OFF Control by Enable

SIGNAL RETURN and ENABLE control are isolated from the output terminals and"-SENSE".
3.2.4

Output Voltage Programming by Built-in Potentiometer

Output Voltage of RFE1600 Series can be trimmed by potentiometer between approximately 80%-120% for
24V, 32V, 48V and 80%-110% for 12V of nominal output voltage (For Output voltage limits see Graph below).
3.2.5

Output Voltage Programming by PMBus (Optional)

Output Voltage of RFE1600 Series can be programmed by PMBus between approximately 80%-120% for 24V, 32V, 48V
and 80%-110% for 12V of nominal output.
RFE1600
ENABLE
J1-8
SIGNAL RETURN J1-17
Figure 3–4:
RFE1600
Figure 3–5:
Control by Ex. Potentiometer
Vout
Voltage Trimmer by Potentiometer
60
50
40
36
30
24
20
18
10
9.6
0
0%
Potentiometer position
Figure 3–6:
Output Voltage Limits
RFE1600
V_REF
V_PROG.
Figure 3–7:
Programming by PMBus
Switch closed: Output ON
Switch open:
Output OFF
Control by ENABLE
V_PROG
J1-3
TRIM
J1-12
59
RFE1600-48
48
39.5
RFE1600-32
RFE1600-24
29
32
24
RFE1600-12
13.2
12
........
50%
100%
J1-5
J1-3
13
Inhaltsverzeichnis
loading

Inhaltsverzeichnis