Example for settings: Protection during absence for doctor's offices, business, company
buildings, etc.
Weekday Mo - Fr: Cut-off time: 8 pm, Opening time 8 am
Weekend Sa - Su: protected except during cleaning on Sa 10 am – 12 pm
Timer01 / Open time: 08:00:00 / Open weekday: Mo,Tu,We,Th,Fr,_ _ / Close time: 20:00:00 /
Close weekday: Mo,Tu,We,Th,Fr,_ _
Timer02 / Open time: 10:00:00 / Open weekday: _ _ _ _ _ _ Sa / Close time:12:00:00 /
Close weekday: _ _ _ _ _ _ Sa
Example for settings: Flushing potable water systems
Flushing should be undertaken weekdays on Mo, We, Fr and Saturday, each at 8 am for 5 minutes.
Timer01 / Open time: 08:00:00 / Open weekday: Mo _ We_ Fr _ Sa / Close time: 08:05:00 / Close
weekday: Mo _ We_ Fr _ Sa
3.6

Acknowledging the alarm

If there is a backflow, the Free Drain Float Switch
(Figure 688 00) will trigger the alarm and the
controller will close the valve.
After remedying the backflow cause, the valve can
be released again via the error acknowledgment.
30/ 32 – K410068602012-00 / 11.2021 – © www.kemper-olpe.de
After acknowledging the control returns to the
previously set operating mode.