3.2 Design and components
No. Components
1
Adaptor 1" male thread x 130 mm for
compact heat/cold meter
2
Stainless steel plate heat exchanger
4
Fill and drain ball valve
5
Shut off ball valves
6
Wall-mounted suspension brackets
7
Insulated hybrid housing
9
Pump for secondary circuit
10
Expansion vessel for secondary circuit
11
Strainer
12
Flow rate controller Ballorex Dynamic
13
Overpressure valve for secondary circuit
½" x ¾"
36
Actuator (on/off)
37
Manometer for secondary circuit ¼"
41
Electrical connection box
42
Electrical connection wiring
Note: The compact heat/cold meter is available as an optional extra from Meibes with and without
data communication via M-Bus.
8
GB
Reference
For optional cold meter (also available with
M-Bus)
S-Line LogoCool 1-5 kW: 36 plates
S-Line LogoCool 2-12 kW: 36 plates
S-Line LogoCool 5-16 kW: 60 plates
M-Line LogoCool 9-24 kW: 50 plates
½"
Optional as required, diffusion-tight insulation
GF UPMXL 25-125 (25-105 at 1-5 kW) 180 AUTO,
grey cast iron
2 litre, ½" male thread
S-Line = 1" male thread; M-Line = 1 ¼" male
thread
S-Line LogoCool 1-5 kW: DN15S
S-Line LogoCool 2-12 kW: DN15H
S-Line LogoCool 5-16 kW: DN20H
M-Line LogoCool 9-24 kW: DN25H
3 bar
Thermoelectric actuator, type NC, 230 V
4 bar
230 V / 50 Hz