the cable entries are tightened firmly
the lamps are inserted correctly
the luminaire is sealed according to regulations
unused cable entries are sealed with plugs and unused holes are sealed with stopping
plugs
Danger due to non-certified accessories!
Explosion protection is endangered!
Cable entries, plugs and stopping plugs must:
• be suitable for the operating conditions (see type label)
• have the technical accordance regarding the listed standards in the certificate
of light fitting or be certified separately
Insulation test of the lighting system
An insulation measurement of direct voltage in electric circuits with the luminaire is 
permissible up to 1000 V DC, measuring current 1 mA:
between
between
between
For a successful measurement between L and N, the electronic ballast must be 
disconnected from the mains, i.e. disconnect this luminaire from supply by actuating the
central lock of the luminaire by means of the disconnector.
Permitted : U = max. 1000 V DC/1 mA
Do not forget:
Reconnect the N conductor before applying voltage!
When carrying out insulation measurements, the disconnect terminal of the 
N conductor may be opened only if the mains voltage is disconnected!
Before commissioning, make sure that the connection of the N conductor is correct!
During operation of the lighting system, do not disconnect the N conductor alone/first!
222203 / 600160300010
2013-05-21·BA00·III·en·00
N and PE conductors
L and PE conductors
L conductor and N conductor not allowed and also not appropriate as
the input wiring of the electronic ballast is measured and thus incorrect
results are produced.
N
L
U
PE
WARNING
N
L
U
PE
Light Fittings for Fluorescent Lamps
Series EXLUX 6001
Commissioning
N
L
PE
06049E00
17