Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - Stahl EXLUX 6001 Serie Betriebsanleitung

Leuchte für leuchtstofflampen
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Electrical connection L, N
In opened end position and with lighting trough hinged away, an anti-pumping device
prevents the central lock from being actuated.
Please do not use force!
When the lighting trough is closed, the central lock is released.
Opening and closing the reflector plate
Danger due to live components!
Risk of fatal injuries!
All connections and wiring must be disconnected from the power supply.
Secure the connections against unauthorized switching.
Open the reflector plate by pressing the safety latch. Swivel the reflector plate.
When closing, flip up the reflector plate and snap into place.

Electrical connection

Observe the maximum clamping possibility of the connecting terminals (see chapter
"Technical data"). In optional screw-type terminals, two conductors per clamping unit can
be clamped (ingoing and outgoing wiring).
Note:
Clamping at the "Ex e" terminal must be carried out very carefully.
Do not clamp any part of the conductor insulation!
Do not interchange the conductors!
Observe the technical regulations when connecting the conductor!
The conductor must be firmly clamped.
For optional screw-type terminals: Firmly tighten screws (2 Nm or 0.7 Nm for clamping
units unused) and check!
You do not need to remove the terminal covering of the optional screw-type terminal
to clamp the conductor!
Ensure that the maximum permissible conductor temperatures are not exceeded by
performing a suitable selection of electric lines used and means of running them!
222203 / 600160300010
2013-05-21·BA00·III·en·00