– Insert the rotary handle into the internal gear of the
actuator so that the handle and the marking on the
stem are in line in the direction of flow.
– The ball valve, rotary handle and actuator are now
aligned in the "open" position.
– In case of horizontal installation of the actuator, the
marking on the rotary handle also has to be in line
with the marking on the stem in the direction of flow.
– Screw the actuator onto the ball valve by tightening
the hexagon socket screw with the help of the
enclosed clamp handle or an Allen key (size 3).
All manuals and user guides at all-guides.com
– After having tightened the screw, the clamp handle
has to be inserted into the rotary handle.
NOTE
Control of the correct positioning of the actuator
on the ball valve is part of the initial operation and
is described under paragraph 8.5
NOTE
Deposits and abrasive substances in the potable
water may impair function. A filter with a mesh
size ≤ 140 µm which is suitable for potable water
should be installed on the cold water side.