6.3 Fitting of the actuators onto the ball valves
– The transformer for the actuators must not yet
be connected to the power supply.
– The actuators are addressed and carry the following
markings on the lateral right hand side:
Master = 1
Slave = 2 / 3 / 4
– Each actuator must only be used once within
one cascade.
– The actuators open through an anticlockwise
rotation and close through a clockwise rotation.
– The actuator is disengaged by pressing the manual
override button a; manual adjustment of the actuator
is possible in this position, see illustr. 4.
Illustr. 4: Manual override button
– Press the manual override button a and keep it
pressed. Press the lock catch b on the left hand
side of the manual override button to lock the
pressed override button, see illustr. 5.
b
Illustr. 5: The manual override button a was pressed
and locked with the help of the lock catch b.
The actuator is disengaged.
40
All manuals and user guides at all-guides.com
– Set internal gear to the "open" position by turning
– Now the rotary movement limiter (sheet metal ring
– Release manual override button a by pressing it
a
– Remove rotary handle from the actuator.
Positioning of the actuators:
The master actuator no. 1 is mounted onto the
ball valve nearest to the distribution box. The slave
actuators 2, 3 and 4 are mounted in sequence.
This sequence must strictly be followed
See system example 4.5.
– Press the aligned actuator in a vertical position
a
the rotary handle anticlockwise.
with stop dogs) has to touch the left stop, see 2 in
the below sketch:
once.
NOTE
(writing faces upwards) onto the aligned and
vertically mounted ball valve whilst holding the
mechanical stop ring tight.