Herunterladen Inhalt Inhalt Diese Seite drucken

Gemü Q50 eSyStep Betriebsanleitung Seite 87

Elektromotorisch betätigtes schlauchquetschventil
Vorschau ausblenden Andere Handbücher für Q50 eSyStep:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

11.4.31 Operating times
The current valve travel times can be read out with the Operating times parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x62
1
0
RO
2
8
RO
Description of parameter values
Index name
Operating times
11.4.32 Drive sets
The traverse speed and force of the actuator can be influenced with the Drive sets parameter when the valve is initialized.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x90
1
0
R/W
2
8
R/W
Description of parameter values
Index name
Drive sets
Speed
Actuator size
AG0 and AG1
Force settings
Actuator size
AG0 and AG1
11.5 Events
The following IO-Link events can be transmitted.
Device Hardware Fault
Motor Unable To Move
Device Temperature Over-Run
Emergency Power
Primary Supply Voltage Under-Run
www.gemu-group.com
Length
Index name
8 bits
Operating times
8 bits
Parameter
Open
Close
Length
Index name
2 bits
Drive sets
3 bits
Parameter
Speed
Force
Event
Parameter
Open
Close
Values
0 to 255
Read out operating time (in tenths of seconds) from end pos-
0 to 25.5 s
ition CLOSED to end position OPEN.
0 to 255
Read out operating time (in tenths of seconds) from end pos-
0 to 25.5 s
ition OPEN to end position CLOSED.
Parameter
Speed
Force
Values
1 ... 3
Select the speeds for the average travel range.
1 ... 6
Set the force for the average travel range and for sealing.
Preset at the factory depending on the valve type.
Setting parameter
1 (43 %)
2 (71 %)
3 (100 %)
Setting parameter
1
6
Mode
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
87 / 100
11 Specific data IO-Link (pin 6)
Type
Default
uint:8
0
uint:8
0
Description
Type
Default
3
-
Description
Average speed in mm / s
1.6
2.3
3.0
Force
Minimum force
Maximum force
Type
Error
Error
Warning/Error
Warning
Error
Values
0 to 255,
0 to 25.5 s
0 to 255,
0 to 25.5 s
Values
1 ... 3
1 ... 6
Code
0x5000
0x8CE0
0x4210
0x5100
0x5111