Technical information / Functioning / Parameters

Switching functions of the transistor output:
4 settings can be selected: Hno = hysteresis / normally open
Configuration of output 2 (analog output)
2 functions can be set:
I = 4 ... 20 mA / U = 0 ... 10 V
Min-Max memory:
• HI: Displays the highest measured level
• LO: Displays the lowest measured level
Erase the memory
- Press the "Mode/Enter" button until "HI" or "LO" is displayed.
- Press the"Set" button and keep it pressed until "- - -" is displayed.
- Then press the "Mode/Enter" button briefly.
Offset (basic value for display and measured value):
The area between the bottom of the vessel and lower face of the measuring probe can be
entered as offset value. Thus the display and switch points refer to the real vessel level.
setting range
LK3022
LK3023
LK3024
Display unit:
2 settings can be selected: EU = display in cm (Europe)
Select the display unit before setting the switch points (SPx, rPx).
This avoids rounding errors generated internally during the conversion of the units and enables
exact setting of the values.
Hysteresis
All manuals and user guides at all-guides.com
Hnc = hysteresis / normally closed
Fno = window function / normally open
Fnc = window function / normally closed
cm
0 ... 78
0 ... 57
0 ... 186
inc = display in inch
The hysteresis keeps the switch-
ing state of the output stable if
the level varies about the preset
value. When the level is rising,
the output switches when the
switch-on
point
has
reached (SP1); when the level is
falling again, the output switches
back when the switch-off point
(rP1) has been reached.
The hysteresis can be adjusted:
First the switch-on point is set, then the switch-off point with the
requested difference.
inch
0 ... 30.6
0 ... 22.4
0 ... 74.5
P
SP
rP
been
1
0
1
0
in steps of
0.5cm / 0.2inch
0.5cm / 0.2inch
1.0cm / 0.5inch
hysteresis
t
Hno
Hnc