Installation and set-up / operation

After mounting, wiring and setting check whether the unit operates
correctly
Faults displayed during operation:
Overload (above measuring range of the sensor).
Underload (below measuring range of the sensor).
Flashing: short circuit in the switching output 1*.
Flashing: short circuit in the switching output 2*.
Flashing: short circuit in both switching outputs*.
*The output concerned is switched off as long as the short circuit exists.
Technical information / Functioning / Parameters
Adjustable parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is auto-
matically reduced (rPx is set to the minimum setting value).
rP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Setting
range
bar
PSI
MPa
1)
Measured value = displayed value * 10
2)
display -.XX = -0.XX
∆P = increments
All manuals and user guides at all-guides.com
SP1 / SP2
min
0.0
1)
0
2)
0.00
rP1 / rP2
max
min
100
-0.5
1450
-10
10.0
-0.05
∆P
max
99.5
0.1
1440
10
9.95
0.01
27