Technical informations / Functioning / Parameters

Adjustable parameters

Switch-on point 1 / 2:
Upper limit value at which the output changes its switching
status.
Setting range → page 37.
SP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching sta-
tus.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is auto-
matically reduced (rPx is set to the minimum setting value).
Setting range → page 37.
rP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
Configuration of output 2
4 switching functions and the diagnostic function can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- dESI = Output 2 is used as a diagnostic output
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button
briefly.
If the submenu is protected with an access code,"Cod1" flashes
in the display.
- Press the "Set" button and hold it pressed until the valid code
no. is shown.
- Then briefly press the "Mode/Enter" button.
Delivery by ifm electronic: no access restriction.