Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic efector 160 LK3 Bedienungsanleitung Seite 27

Elektronische fullstandssensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Applications
Pumping station
OFS
Page 28
All manuals and user guides at all-guides.com
Empty the vessel with overflow protection
Switching output (OU1): overflow protection
maximum value exceeded → alarm
slightly below SP1 (to suppress wave movements)
hysteresis function, normally closed (Hnc)
Analog output (OU2): control to empty vessel
I (4 ... 20mA) or U (0 ... 10V)
L
SP1
rP1
OUT1
1
Hnc
0
10V / 20mA
OUT2
U / I
0V / 4mA
If the level is below SP1, output 1 switches. If SP1 is exceeded or if
there is a wire break, output 1 switches off (
By the analog signal the maximum level can be controlled (submersible
pump ON / OFF).
overflow protection
alarm).