Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic efector 160 LK3 Bedienungsanleitung Seite 20

Elektronische fullstandssensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation
Mounting elements
Mounting
recommendation
Special mounting
conditions
All manuals and user guides at all-guides.com
Mount the unit with-
in the inactive zone, if
possible (I; mounting
area M1). The active
zone (A) should be
completely in the ves-
sel.
For an optimum func-
tion we recommend:
A part of the active
zone should be above
the upper edge of the
vessel / above the
overflow (1cm for
LK3022 / 1.5cm for
LK3023 / 2.5cm for LK3024).
You can also fasten mounting elements in the upper half of the active
zone (possible mounting area, M2). This reduces the active zone to the
area between mounting element and probe end. In this case the
mounting element should be above the upper edge of the vessel /
above the overflow (3cm for LK3022 / 5cm for LK3023 / 8cm for
LK3024).
• If possible, mount the unit in the middle of the vessel when it is
installed in small plastic vessels:
• For dirty media we recommend: Fasten the unit in a zone where
there is much movement of the medium (e.g. at the supply inlet).
• When installed in metal rising pipes (bypass) the sensor must be
mounted in the middle of the pipe. The inside diameter of the pipe
must be min. 120 mm.
• Metal objects within the vessel
(e.g. metal pipes, components
integrated into the vessel)
must observe a minimum dis-
tance of 60 mm to the active
zone of the sensor. Otherwise,
they are detected as mounting
element (this reduces the
active zone to the area
between metal object and
probe end).
• When installed in metal vessels
the following distances must
be observed:
- sensor - vessel wall: 40mm
- sensor - vessel bottom:10mm
min. 60mm
B
min.
40mm
min.
10mm
A = active zone
B = metal component
Page 21

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis