Herunterladen Inhalt Inhalt Diese Seite drucken

Vortice VORT NRG EC 3000 Bedienungs- Und Inbetriebnahmeanleitung Seite 24

Vorschau ausblenden Andere Handbücher für VORT NRG EC 3000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ENGLISH
VII.2 Tree structure of menus
Words written normally = view only / Words in bold = Modification possible / Words in bold underlined = Modification
possible with password 3333. = not used or not accessible.
!
NOTE: Do not change parameters other than those shown in bold, otherwise no After-Sales Service can be
included.
MODE OF REGULATION
Year:month:day
Time
System:start oper. or stop
SP: T°C set point Act.: T°C current
Operating mode
CORRIGO E
Ventilation
Made by
VORTICE
Operating mode
. . .
Alarm report
Inputs/outputs
Ventilation
Version:
ID number:
Operating mode
Auto (6)
Operating
period
Vent. AS: 00.0 hours
Operating
period
Vent. AR: 00.0 hours
Viewing the alarm log
(use the bottom arrow to scroll the
log)
AI
Analogue inputs
DI
Digital inputs
UI
Universal input
AO
Analogue outputs
DO
Digital outputs
AI1: AS Temp. (supply air)
AI2: Ext. Temp. (outdoor)
AI3: Def. temp. (defrost)
AI4: AR Temp. (return air)
DI1: Mar Ind. Func. AS
DI2: Mar Ind. Func. AR
DI3: Filter alarm
DI4: Overheating
DI5: Forced start 1/1
DI6: Forced start 1/2
DI7: External stop
UAI1: Sup. loop temp.
(exchanger input - INFINITE)
UAI2: AS Press.
(LOBBY / MAC2 & QUATTRO)
UAI3: AR Press.
(LOBBY / MAC2 & QUATTRO)
UAI4: CO2 (DIVA / QUATTRO)
AO1: Heating
AO2: Exchanger
AO3: Cooling
AO4: Vfr AS
AO5: Vfr AR
DO1: AS Vfr start
DO2: AR Vfr start
DO3: AS damper
DO4: AR damper
DO5: Alarm total
DO6: Defrost start (INFINITE)
24