Test Run & Fault Code

Before test run

• Before switching on the unit, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm
meter and check if the resistance is above 1MΩ. The unit cannot be operated if it is below1MΩ.
• Connect the unit to the power supply of the outdoor units to energize the heating belt of the compressor. To protect the
compressor at start-up, power it on 12 hours prior to theoperation.
• Review the test run procedures in the outdoor unit and ensure that the outdoor unit has been properly installed
according to the instructions in the outdoor manual.
Check that all piping has been installed, connected and insulation in accordance with the instructions provided
in the manual.
check if the mains voltage matches
check if there is leakage at the piping joints
check if the connections of mains power and indoor &
outdoor units are correct
check if the serial numbers of the terminals match
check if the installation place meets requirements
Test run method
• Ask the installation personnel to conduct a test run. Conduct the testing procedures according to the manual and check
if the temperature regulator works properly.
• When the machine fails to start due to the room temperature, the following procedures can be undertaken to conduct
compulsive running. This function is not provided for the type with remote control.
• Set the wired controller to cooling/heating mode, press 'ON/OFF' button for 5 seconds to enter into the compulsive
cooling/heating mode. Press the 'ON/OFF' button again to quit compulsive running and stop the operation of the air
conditioner.
Fault remedies
• When any fault appears, consult the fault code of the wired control or the flashing times for LED5 on the indoor unit
board, and find the faults as shown in the following table to troubleshoot.
• Indoor unit faults
Failure code at
PCB LED5 (Indoor Units)
wired controller
/ Receiver Timer Lamp
(RemoteController)
1
1
2
2
3
3
5
5
6
6
7
7
8
8
9
9
14
14
18
18
20
20
check if there is too much noise
check if the connecting line is fastened
check if the connectors for tubing are heat insulated
check if the water drains outside
check if the indoor units are positioned
Fault Descriptions
Fault of indoor unit ambient temp. transducer TA
Fault of indoor unit pipe temp. transducer TC1
Fault of indoor unit pipe temp. transducer TC2
Fault of indoor unit EEPROM
Fault of communication between indoor & outdoor units
Fault of communication between indoor unit and wired control
Fault of indoor unit water drainage
Fault of duplicate indoor unit address
Fault of DC MOTOR
Fault of BS valve box or 4MV Reverse
Corresponding faults of outdoor units