10 - CONNECTIONS

When following these steps, please consult the dimensional drawing and connection diagram as well as the wiring diagram found
inside the unit.

10.1 - Hydraulic connection

The hydraulic pipes must be routed through the plates provided for this purpose in the unit frame. This is either done to the right of
the unit or directly underneath.
These plates must be drilled (water circuit + condensate draining) then refitted in place before the hydraulic pipes are routed through
them.
For the W115 model, the pipes on the right are routed through a fixed insulated panel.
please see the dimensional drawing and connection diagram to locate the routing areas and connection positions
Connection diameters:
Cooling coil
Heating coil
Always use two spanners when connecting or tightening the hydraulic couplings to avoid twisting the pipes and applying stress on the
welds.
To avoid the risk of condensation, the hydraulic pipes and elements must be carefully insulated.
Before insulating, check the tightness of the couplings.
Warning
: the operating pressure on the chilled or hot water network must not exceed 8 bar.
Once all the connections have been made, the access holes must be sealed.
Insulated flexible connections are available on request for carrying out hydraulic connections. Ensure these are not bent too acutely
to avoid pinching the inner tube and restricting the flow of water.

Condensate drain

The condensate drain pan should include a siphon to avoid any risk of overflowing.
(See position and connection diameter on the dimensional drawing).
In these units, the pan is depressed due to its position in relation to the fan motor assembly.
To enable correct drainage, the height must be equal to at least twice the unit's depression.
44
W40
Inlet
G 1"1/4 (M)
Outlet
G 1"1/4 (F)
Inlet
Outlet
side plate
Foam panel
W53
W78
G 1"1/4 (M)
G 1"1/2 (M)
G 1"1/4 (F)
G 1"1/2 (F)
W40
W53
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
W100
W115
G 1"1/2 (M)
G 1''1/2 (M)
G 1"1/2 (M)
G 1''1/2 (F)
W78
W100
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)