Installation Procedures
Fan Static pressure adjustment
The blower can be set for the maximum static pressure and standard static pressure air volume through the controller,
which is set to the standard static pressure at the factory. Based on the duct design and filter selection the static
pressure will need to be adjusted, the static pressure selection is performed as follows:
Remote controller setting mode: remote control selects static pressure in high fan speed , press the health button12
times within 5 seconds, the buzzer will reverberate 4 times, set the maximum static pressure successfully. Press the
health button 12 times within 5 seconds. The buzzer will sound 2 times, the maximum static pressure function will be
cancelled, and the default setting will be restored.
YR-E17WiredController setting mode: keep pressing the key Set and the key
advanced setting, press the key Fan to switch to the function category b(temperature zone display),at this time
function category code flashes(clock zone display),press the key
Set. The existing static pressure display is performed in the time zone and the specific information flashes. While it is
flashing, press the key
the default standard static pressure, O2 means the maximum static pressure.
Static Pressure Range
unit: Pa
Model
40VD005-028S-7S-QEE
40VD030-054S-7S-QEE
4. Drainpipes
gas pipe
(a) Keep a gradient (1/5O-1/1OO)of the drain pipes and avoid lobing or curving.
• Proper Piping
hanging bolt
1.5m ~ 2m
Heat insultor
gradient of 1/1OO or over
or
to change it. After the change is completed, press the key Set to confirm. O1 means
Standard Static Pressure
20
20
347mm
liquid pipe
or
to switch the value to 11, then press the key
Max. Static Pressure

drainpipe

• Improper Piping
air outlet port
8
minus 5 seconds to enter the
200
180
avoid lobing
avoid curving
Do not put pipe
into water