and to the actual electrical consumption of all the equipment to be connected to the
system.
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +55°C without batteries, 0°C to
+40°C with batteries, suggest to storage the battery below 25°C.
This UPS can be used in TN/IT/TT power system
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation in
rack system).
Before and after the installation, if the UPS remains de-energized for a long period, the
UPS must be energized for a period of 24 hours, at least once every 6 months (for a
normal storage temperature less than 25°C). This charges the battery, thus avoiding
possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and
number of elements as the original Battery Module provided with the UPS to maintain
an identical level of performance and safety.
This is a category C2 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.