Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Specifications; Operating Limits; General Notes On Delivery; Handling And Storage - Sabiana Carisma Whisper CFF-ECM Anweisungen Für Installation, Gebrauch Und Wartung

Klimakonvektoren
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 63
EN
1.3
Coil connections positions
Filter (E)
Made of regenerable synthetic material removable
from below.
Condensate collection tray (F)
Made of plastic, it has the function of collecting the
condensate produced by the unit during the sum-
mer cooling phase and conveying it to the external
auxiliary tray equipped with hose connection.

Technical specifications

A-weighted sound pressure level < 70 dB(A).
For dimensions, weights and water content, see
p. 109

Operating limits

Fan coil unit
The basic specification of the fan coil and heat ex-
changer is given below:
Description
Highest working
pressure
Lowest water inlet
Water flow
temperature
Highest water inlet
temperature
Single-phase rated
Power supply
operating voltage
Electric energy consumption: see technical data
label.
Valves
The technical specification of the valves with ther-
moelectric actuator is given below:
26
Other technical data
All other important technical data (dimensions,
weights, connections, noise emissions, etc.) are giv-
en elsewhere in this User Information Manual, in the
separate technical documentation or in the technical
proposal.
Water flow rate limits for 2 row coil

General notes on delivery

Notes for the installer.
The unit is supplied in cardboard packaging.
After removing the packaging, make sure the con-
tents are as requested and not damaged, and that
UoM
Value
the machine components have not been damaged
bars
10
by impacts.
kPa
1000
Control if the threading of the tubes, which are pro-
truding from the unit, is all right.
°C
+6
In the event of damage or if the identification code
°C
+85
does not correspond to that ordered, contact your
dealer immediately, quoting the series and model.
V/Hz
230/50-60

Handling and storage

Notes for the installer.
The units must be handled by at least two persons.
Description
Water flow
Highest working pressure
Maximum glycol content in water
Highest water inlet temperature
Power supply
Single-phase rated operating voltage
VA rating
IP protection
Initial opening and closing time
CFF-ECM
Model
10
Water flow rate
l/h
40
Min.
Water flow rate
l/h
200
Max.
UoM
Value
bars
10
kPa
1000
%
50
°C
85
V/Hz
230/50-60
VA
2,5
IP
44
Seconds
75
CFF-ECM
CFF-ECM
CFF-ECM
CFF-ECM
20
30
40
80
120
350
500
600
50
800

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis