Herunterladen Inhalt Inhalt Diese Seite drucken

SMA NR-STP200-ACCON Austauschanleitung Seite 20

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 33
5 Disconnecting the Inverter from Voltage Sources
8. Remove all 6 screws from the lower enclosure lid
using an Allen key (AF 3).
9. Lift and remove the lower enclosure lid from below.
10.
Risk of burns when touching the enclosure parts
The enclosure parts become hot during operation. Touching these components can cause
burns.
• After switching off the inverter, wait until any hot enclosure parts have cooled down
before touching them.
11. Note the position of the DC connector in order to be able to connect it again later in the same
position.
12.
Danger to life due to electric shock when touching exposed DC
conductors or DC plug contacts if the DC connectors are damaged or
loose
The DC connectors can break or become damaged, become free of the DC cables, or no
longer be connected correctly if the DC connectors are released and disconnected
incorrectly. This can result in the DC conductors or DC plug contacts being exposed.
Touching live DC conductors or DC plug connectors will result in death or serious injury due
to electric shock.
• Wear insulated gloves and use insulated tools when working on the DC connectors.
• Ensure that the DC connectors are in perfect condition and that none of the DC
conductors or DC plug contacts are exposed.
• Carefully release and remove the DC connectors as described in the following.
20
STP8-17-STP15-20TLEE-AC-CON-RM-xx-10
CAUTION
DANGER
SMA Solar Technology AG
Replacement Manual

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Nr3-stp200-accon

Inhaltsverzeichnis