5 - Specifications
Electrical output specifications when running on mains power
MEGALINE
1250
Nominal output
voltage
Nominal output
frequency
Output current with
linear load and
5,37A rms
power factor 0,7
Crest factor on
output current
1250VA
Nominal output
power VA
Active output power
875W
with linear or non-
linear load P.F. 0,7
Total harmonic
distortion of output
voltage with
nominal load
Total harmonic
distortion of output
voltage with
nominal non-linear
load P.F.0,7
Overload
capacity
Number of output
phases
AC-AC conversion
efficiency with
linear load PF = 1
and charged
batteries:
•with 50% load
•with 75% load
•with 100% load
All manuals and user guides at all-guides.com
MEGALINE
2500
50 Hz / 60Hz synchronised (autosensing and/or as selected by operator)
10,75A rms
2500VA
1750W
300% for 1 second without By-pass intervention
200% for 5 seconds without By-pass intervention
150% for 30 seconds without By-pass intervention
49
MEGALINE
3750
230 V ± 1%
16,25A rms
3,5
3750VA
2625W
< 0,5%
< 1%
Single phase
80%
85%
92%
MEGALINE
5000
21,6A rms
5000VA
3500W