MEGALINE
1250
Nominal input
voltage
Input voltage
range
Nominal input
frequency
Nominal input
4,6A rms
current
Maximum input
5,75A rms
current
Distortion of input
current
Input power
factor
In-rush current
Number of input
phases
Line fuse
Battery charger
directly from mains
MEGALINE
1250
With mains
operation
With battery
operation
Type of
operation
All manuals and user guides at all-guides.com
Electrical input specifications
MEGALINE
2500
from 184V to 264V with nom. load – from 100V to 264V with 50% of nom. load
50 Hz or 60 Hz +/-2% (autosensing and/or as selected by operator)
8,9A rms
11,2A rms
> 0,99 dal 20% of nominal load
100% of nominal current
Output wave form
MEGALINE
2500
No break, on line UPS with passing neutral and double conversion
MEGALINE
3750
230 V
13,2A rms
16,6A rms
THD
< 3%
Single phase
25 AFF
0,8 A rms
MEGALINE
3750
Sine wave
Sine wave
48
5 - Specifications
MEGALINE
5000
17,7A rms
22,2A rms
MEGALINE
5000