Input
Power
xxxx
Appar.Pow.
xxxx
V RMS
xxx
➧
I RMS
xxxx
Peak Current
x
Frequency
x
I Crest factor
x
Power Fact
x
Batteries
Voltage
xx
Residual Cap. xxxx
➧
xxxx
Discharge count
Usage
xxxx
Cal.dd/mm/yyhh:mm
Ext. KB units
xx
Ext Chargers
xx
History Data
UPS Ontime
xxxxx
➧
BoosterOnTime
xxxx
DrainedOut N.
xxxx
Booster Int.
xxxx
Bypass Interv.
xxxx
OverheatCount xxxx
All manuals and user guides at all-guides.com
Power
Indicates the power received from mains (W)
Appar. Pow.
Indicates the apparent power received from mains (VA)
V RMS
Indicates the effective voltage (V RMS) at the UPS input
Indicates the effective current (A RMS) received from
I RMS
mains
Peak Current
Indicates the peak current received from mains (A)
Indicates the frequency of the UPS input voltage (Hz)
Frequency
Indicates the crest factor, calculated as the ratio between
I Crest factor
the peak value and the effective value of the current
received from mains
Power Fact
Indicates the power factor applied to mains
Voltage
Indicates the voltage at the terminals of the battery kits (V)
Residual Cap.
Indicates the percentage of battery charge
Discharge
Indicates the number of battery discharge cycles
Count
Hours of operation on battery power
Usage
Cal..
Indicates the date (day / month / year) and the time
(hours / minutes) of the last battery calibration
Ext. KB units
Indicates the number of external KBs fitted
Indicates the number of external battery chargers fitted
Ext Chargers
(the MetaSystem CB36)
UPS Ontime
Indicates the total number of hours of UPS operation
BoosterOnTime
Indicates the number of hours of UPS operation in booster
mode (running on battery power)
Indicates the number of times the UPS has completely
DrainedOut N.
discharged its batteries.
Booster Int.
Number of times booster mode has intervened (running on
battery power)
Bypass Interv
Number of times the by-pass has intervened (refer to
Config.UPS / By-pass menu)
Number of times the thermal protection has been triggered
OverheatCount
(due to excessive load, for example)
40
4 - Customising the UPS operating mode