12 Device Information

1
Type and order code
2
Design
2.1
Model
2.2
Degree of protection according to EN 60 529
2.3
Installation location
1
3
Performance data
3.1
Operating temperature limits:
2
Heating water flow
Cooling, flow
Brine (heat source, heating)
Brine (heat sink, cooling)
Antifreeze
Minimum brine concentration (-13 °C freezing temperature)
3.2
Heating flow / internal pressure differencial
Nominal flow according to EN 14511 at B0 / W35-30
Minimum flow
3.3
Heat output / COP
3.4
Cooling flow / internal pressure differencial
Nominal flow according to EN 14511 at B30-35 / W7-12
Minimum flow
3.5
Cooling capacity / COP
3.6
Sound power level according to EN 12102
3.7
Sound pressure levelat a distance of 1 m
3.8
Refrigerant / total filling weight
3.9
GWP value / CO
equivalent
2
3.10 Refrigeration circuit hermetically sealed
3.11 Lubricant / total filling weight
4
Dimensions, connections and weight
4.1
Device dimensions without connections
4.2
Device connections to heating system
4.3
Device connections to heat source
4.4
Weight of the transportable unit(s) incl. packing
5
Electrical Connection
5
5.1
Nominal voltage
/ fuse protection
5.2
Control voltage / Fuse protection
5.3
Nominal power consumption B0W35
5.4
Starting current with soft starter
5.5
Nominal current B0 W35 / cos
www.gdts.one
°C
°C
°C
°C
m³/h / Pa
at B0 / W45-40
m³/h / Pa
at B0 / W55-47
m³/h / Pa
m³/h / Pa
at B-5 / W55
kW / ---
at B0 / W55-47
kW / ---
at B0 / W45-40
kW / ---
at B0 / W35-30
kW / ---
m³/h / Pa
at B30-35 / W18-23 m³/h / Pa
m³/h / Pa
at B30-35 / W7-12
kW / ---
at B30-35 / W18-23 kW / ---
at B20 / W8
kW / ---
at B20 / W18
kW / ---
at B10 / W8
kW / ---
at B10 / W18
kW / ---
dB(A)
3
dB(A)
type / kg
--- / t
type / litres
4
H x W x L mm
inch
inch
kg
V / A
V / A
1
/ max. consumption kW
A
A / ---
452232.66.41 · FD 9912
SI 10MER
Reversible
IP 21
Indoors
+20 to +62 ±2
+7 to +20
2
-5
to +25
+5 to +40
Monoethylenglykol
25 %
Brine
2.4 / 15800
2.4 / 15800
1.9 / 9600
1.9 / 9600
7.6 / 2.3
8.9 / 2.7
9.3 / 3.3
9.7 /4.3
Brine
2.5 / 17100
3.0 /24700
2.4 / 15800
10.7 / 4.3
13.4 / 5.2
12.1 / 6.2
14.5 / 7.2
12.6 / 8.1
14.7 / 9.2
49
37
R410A / 2.0
2088 / 4
yes
Polylester / 1.2
800 x 650 x 450
G 1¼" a
G 1¼" a
121
1~/N/PE 230 V (50 Hz) / C25 A
1~/N/PE 230 V (50 Hz) / C13 A
2.28 / 4.05
44
10.4 / 0.95
English
Heating water
1.7 / 8000
1.7 / 8000
1.0 / 2800
1.0 / 2800
Cooling water
1.9 / 9500
2.3 / 14000
1.7 / 8000
EN-11
loading