14 EN – Quick installation guide

Connect the control cables

Connect the conductors of external control cables to the appropriate terminals of the
control unit. See section
(page 15).
1. Ground the outer control cable shields 360 degrees at the cabinet entry plate
(recommendation).
2. Remove the middle front cover of the drive module.
3. Attach the option modules if not attached already.
4. Remove the cover plate from the control cable entry (4a) and put the rubber grommet
in its place. Put the control cables through the grommet. M4 holes (4b) can be used as
mounting points for cable tie holders. IP20 shrouds (option +B051) are included in the
EN
drawing below. The external control unit (option +P906) is not integrated to the drive
module, see chapter
DA
DE
ES
FI
FR
IT
NL
PL
PT
5. Ground the shields of the control cables at the clamp plate.
RU
SV
TR
6. Connect the conductors to the appropriate detachable terminals of the control unit.
Use shrink tubing or insulating tape to contain any stray strands. Tighten the screws to
ZH
secure the connection. Note: Keep any signal wire pairs twisted as close to the
Default I/O connection diagram (HVAC default configuration)
External control unit (option +P906)
(page 103).