Explanation of the individual output values:
Column 2: current distance: read-out of the respective current measuring distance in mm
Column 3: statuses of the digital outputs:
0: not switched
1: switched
#
#
F
A3
Example: 1001 à error output and output 1 switched.
Column 4: difference between current distance and the selected switching point (for each output)
Example:
Column 5: digital read-out of the current or the voltage value in mV
(depending on the setting in the "Analog" menu)
Column 6: time stamp
Example:
Time Stamp
00001024
00001066
99999999
00000000
By outputting the time-stamp, the individual measurement distances can be assigned to a relative time without
taking into consideration the processing speed of the computer.
Time stamp: D 1 ≙ 500 µs
Sensors for your success
#
#
A2
A1
2000 mm
Measuring Distance
1805 mm
1810 mm
2068 mm
2068 mm
www.wenglor.com
55
Output 1: switching threshold at 2800 mm
Output 2: switching threshold at 1500 mm
Output to interface:
Output 1: -000800
Output 2: +000500