Technical parameters
Supply
Supply terminals:
Supply voltage:
Consumption:
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Backup battery type:
Measuring circuit
Measuring terminals:
Temperature range:
Hysteresis (sensitivity):
Diference:
Sensor:
Sensor failure indication
(overrun):
Accuracy
Measuring accuracy:
Repeat accuracy:
Temperature dependance:
Number of function:
Output
Number of contacts:
Rated current:
Switching capacity:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Time circuit
Real time back-up:
Accuracy:
Minimum interval:
Data stored for:
Program circuit
Number of memory places:
Program:
Data readout:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
2
Max. cable size (mm
):
Dimensions:
Weight:
Standards:
* ERROR - sensor short circuit - the relay is disconnected
NO SENSOR - interruption sensor - the relay is disconnected
TER-9
A1 - A2
AC 230 V (AC 50-60 Hz), galvanically isolated or
AC/DC 24 V, not galvanically isolated
max. 4 VA / 0.5 W
3 W
-15 %; +10 %
CR 2032 (3V)
T1-T1 and T2-T2
-40.. +110 °C
adjustable within range 0.5...5 °C
adjustable 1 .. 50 °C
thermistor NTC 12 kΩ at 25 °C
displayed on LCD *
5 %
< 0.5 °C
< 0.1 % / °C
6
1x switching for each output (AgNi)
8 A / AC1
2000 VA / AC1, 240 W / DC
250 V AC / 30 V DC
symbol ON/OFF
1x10
7
5
1x10
up to 3 years
max. ±1s/ day at 23°C
1 min.
min. 10 years
100
daily , weakly, yearly
LCD display, with back light
-10.. +55 °C
-30.. +70 °C
4 kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP20 clips
III.
2
max. 1x 2.5, max. 2x 1.5 /
with sleeve max. 1x 2.5
90 x 35 x 64 mm
(230V) 150 g, (24V) 113 g
EN 61812-1; EN 61010-1;
EN 60730-2-9; EN 60730-1; EN 60730-2-7
Mode precendence
mode precedence
mode with the highest

priority

ter and Time Program can work at the same time on a single channel.
Control description
Device diff ers short and long button press. In the manual marked as:
- short button press (<1s)
- long button press (>1s)
After 30s of inactivity (from the last press of any button) will device automatically returns
into starting menu.
In the start screen, press
to toggle between displaying the date or measured
OK
temperature.
Language settings
Auto
PRG
Prog
Prog
Prog
language
ter
options
+ _
OK
options
Language
selection
Temperature sensor TC, TZ
Resistance value of sensors based on temperature
Tolerance of sensor NTC 12 kΩ is ± 5% at 25 °C.
TC
TZ
2 / 8
display
output mode
ON / OFF
manual control
ON / OFF 
holiday mode
ON / OFF
time program
ter
thermostat
entrance into programming menu
PRG
browsing in menu
+ _
setting of values
+ _
quick shifting during setting of values
entrance into required menu
confi rmation
OK
switch. between display
one level up
ESC
a step back
back to the starting menu
ESC
ESPAnOL
Prog
Prog
OK
Prog
Prog
+ _
Temperature (°C)
NTC sensor (kΩ)
20
14.7
30
9.8
40
6.6
50
4.6
60
3.2
70
2.3
Prog
Prog
Prog
Prog
language
OK