Menu item
Max. differential
Maximum range
Max diff control
Proportional range
Ramp
Heat source control (setpoint value)
Config mode 0-10V
Input value f. off
Input value f. max.
Max. temp. set v.
Min. temp. set v.
Table 8
Menu EM100 (for RC310 from NF74.xx)
4.4

Fault output

The fault output (OE1-75 and OP0 in coding positions 3-5) is
only activated 10 minutes after the fault has occurred. If no
faults are present, the fault output is deleted immediately.
Faults, which disappear again within the delay time of 10
minutes, are not displayed on the fault output.
24
Settings/adjustment range Remark/restriction
25 ... 40 ... 85 K
1 ... 10 ... 20 K
1 ... 5 ... 20 K
off | 1 ... 5 ... 20 %/s
Temp. | Output
0 ... 10 V
0 ... 10 V
0 ... 90 ... 100 °C
0 ... 20 ... 100 °C
EM100 – 6721804147 (2019/10)
Set maximum temperature differential
Enter width of max. range
Enter width of proportional range
Enter ramp for pump modulation
Boiler control via temperature or output?
Switch off boiler with voltage
Boiler at max. output with voltage
Set max. set temperature