Specification
Rated voltages
BUS
Module mains voltage
User interface
Pump, solenoid valve,
interference output
Fuse
BUS interface
Power consumption – Standby < 3 W
Max. power output
per connection(PC0)
per connection(OE1)
Permitted ambient
temperature
IP rating
Protection class
ID no.
Temperature of ball thrust test 75 °C
Degree of pollution
Table 3
°C
°C
20
12486
50
25
10000
55
30
8060
60
35
6536
65
40
5331
70
45
4372
75
Table 4
Measurements of low loss header temperature
sensor (T0)
18
15 V DC
(reverse polarity
protected)
230 V AC, 50 Hz
15 V DC
(reverse polarity
protected)
230 V AC, 50 Hz
230 V, 5 AT
EMS and EMS plus
400 W (high-efficiency
pumps permissible:
< 30 A for 10 ms)
120 W (high-efficiency
pumps permissible:
< 30 A for 10 ms)
0 ... 60 °C
IP 44
I
Data plate ( Fig. 21 at the
end of document)
2
°C
3605
80
1256
2989
85
1070
2490
90
915
2084
100
677
1753
1480
2.5

Additional accessories

For detailed information about suitable accessories, refer to
the catalogue or Internet page of the manufacturer.
Low loss header temperature sensor; connection to T0
Primary pump; connection to PC0
Installation of additional accessories
▶ Install the additional accessories in accordance with legal
regulations and the instructions supplied.
2.6

Cleaning

▶ Wipe the casing with a damp cloth when necessary. Never
use aggressive or caustic cleaning agents for this.
3

Installation

DANGER:
Danger to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before installing this product: Disconnect the heat source
and all other BUS nodes from the mains voltage across all
poles.
▶ Before commissioning: Mount the cover ( Fig. 20 at end
of document).
3.1

Preparation for the installation in the heat

source
▶ Check by referring to the installation instructions of the
heat source whether it is possible to install modules (e.g.
EM100) in the heat source.
▶ If the module can be installed in the heat source without a
mounting rail, prepare the module ( Fig. 8 and 9 at end
of document).
3.2

Installation locations

▶ Install the module on a wall, ( Fig. 10 and 11 at end of
document), on a mounting rail ( Fig. 12 at end of
document), in an assembly or in the heat source.
▶ When the module is installed in a heat source, observe the
heat source instructions.
▶ Remove the module from the mounting rail ( Fig. 13 at
end of document).
EM100 – 6721804147 (2019/10)