Technical data

Performance data
The table shows the technical performance data for HCH 5 and HCH 8.
Max. air flow at 100 Pa ext. pressure
Heat exchanger
Temperature efficiency
Filter class supply air/exhaust,
standard
Operational temperature range with-
out pre-heat
Operational temperature range with
pre-heat
Cabinet data
The table shows the technical cabinet data for HCH 5 and HCH 8.
Height
Width
Depth (Standard mounting rail/rail
for plan mounting)
Duct connection
Weight, unit
Weight including packaging
Dimensions including packaging
(HxWxD)
Outer cabinet material
Colour
Cabinet insulation, styrene
Insulation factor, cabinet
Fire classification, polystyrene cabi-
net
Fire class, the whole unit
Protection class
1
Condensing operation.
2
Dantherm recommends preheating at temperatures under -6° C to ensure a balanced
operation.
28
Specification
Specification
Unit
HCH 5
(m
/h)
375
3
Dantherm Alu. Counterflow Heat Exchanger
%
ISO Coarse 75% (G4)/
ISO Coarse 75% (G4)
°C
÷13
°C
÷ 30 to + 50
Unit
HCH 5
mm
600
mm
1180
mm
580
mm
160
kg
52
kg
66
mm
H: 740
W: 1200
D: 800
Aluzink
RAL
Aluzink, grey
mm
W/m
x °K
2
DIN 4102 class B1
EN 13501 class E
IP
HCH 8
530
Up to 95
1
to + 50
2
HCH 8
600
1180
780
250
70
84
H: 738
W: 1200
D: 800
40
0,78
20
Continued overleaf