Fittings and installations,
Mounting the unit,
Step
continued
11
12
13
14
15
Drifting snow and
Air inlets and outlets T1 and T4 must be mounted with ducts falling at least fall 1 %
driving rain
away from the unit to prevent drifting snow, driving rain and condensation from enter-
ing the unit causing faults and further damaging the installation and the building.
The warranty does not cover damages to the unit/building parts/insulation, which is
caused by accumulated snow/water in the ducts.
Accessories
In order to mount and install accessories from Dantherm A/S, follow the instruction de-
livered with the accessory.
11
continued
Insulate the entire duct system with 100 mm insulation. For example, place
the ducts below the insulation of the ceiling. If the insulation is wrapped
around the tube, it is recommended to apply two layers of foil.
Wrap the two layers staggered, and tape the area where the two layers meet
until air tight.
Insulate all flex ducts as well as the entire duct system. It is important that es-
pecially the exhaust air duct is insulated, to avoid the possibility of conden-
sate inside the duct, which can lead to water in the unit
Choose the right power supply cable matching the regulation in the actual
country and connect the cable's IEC plug to the unit.
Afterwards connect the unit to 230 V AC
Balance the unit by following the instructions on page 12