Herunterladen Diese Seite drucken

Remote Sensor; Air Removal - RHOSS H58624/B Gebrauchsanweisung

Electa-eco

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 93
2.5.7 Optional E-Heater
At the Commissioning parameter setting page, by touching "Optional E-Heater", the control panel will access to the corresponding setting page.
NOTE
At the "Optional E-Heater" setting page, it can be set:
"1"
=> n°1 electrical heater (KM1 on terminal block)
"2"
=> 2 parallel electric heaters (KM1+KM2 on terminal block)
"Off" => no electrical heater
On "
T-Eheater
" the value of the external air temperature must be set below which the electric resistance can activate (3 ° C
differential).
There are two working logics for "Optional E-heater":
Logic 1: the heat pump and the optional electric heater CANNOT be started at the same time.
Logic 2: the heat pump and the optional electric heater CAN be started at the same time
Either "Other thermal" or "Optional E-Heater" cannot be activated at the same time.
It is necessary connect the water probe RT5, otherwise an alarm appears.
Water probe has to be positioned downstream the electrical heater.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.

2.5.8 Remote Sensor

At the commissioning parameter setting page, by touching "Remote sensor", the control panel will access to the corresponding setting page, where
it can be set to "With" or "Without".
NOTE
Only when "Remote sensor" is set to "With", the "Ctrl. State" can be set to "T-room".
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Without.

2.5.9 Air Removal

At the commissioning parameter setting page, by touching "Air removal", the control panel will access to the corresponding setting page, where it
can be set to "On" or "Off".
The function activates the water pump to allow to vent the system ("Air") or the water tank ("Water tank") from the air.
NOTE
This setting can be done only when the unit is turned off.
When the function is active, the unit is not allowed to be turned on.
The setting is memorized and re-proposed in case of power failure
The default value is Off.
< Save
(see 2.6.1 On/Off memory).
51
ELECTA-ECO

Quicklinks ausblenden:

Werbung

loading

Verwandte Produkte für RHOSS H58624/B