2.2.15 Error Reset

At the Function setting page, by touching "Error reset", a choice box will pop up, where by touching "OK" the error will be reset and by touching
"Cancel" the error will not be reset.
NOTE
It can be performed only when the unit is turned off.
Some errors can only be reset after the cause of the fault has been restored.
2.2.16 WiFi Reset
At the function setting page, by touching "WiFi", a choice box will pop up, where by touching "OK", the WiFi setting will be reset, and by
touching "Cancel" the choice box will quit and WiFi will not be reset.
2.2.17 Reset
At the function setting page, by touching "Reset", a choice box will pop up, where by touching "OK" all user parameter settings will be reset and
by touching "Cancel" it will back to the function setting page.
NOTE
This function is allowed only when the unit has turned off.
This function is valid for "Temp. timer", "Clock timer", "Preset mode", "Weekly timer", and "Weather depend".

2.3 PARAMETER SETTING

At the Menu page, by touching "PARAMETER", it will go to the parameter setting page, as shown in the figure below.
At the menu setting page, by touching the page turning keys, it is able to switch to the page where the desired parameter is.
After that, this setting will be saved by touching "OK" and then the unit will run based on this setting. While this setting will give up by touching
"Cancel".
NOTE
For parameters with different defaults under different conditions, when conditions changes, the default value also will change as the
corresponding condition changes.
This function will be memorized upon power failure (see 2.6.1 On/Off memory).
No
Displayed Name
1
WOT-Cool
2
WOT-Heat
3
RT-Cool
4
RT-Heat
5
T-water tank
6
∆T-Room temp
7
∆T-Cool
8
∆T-Heat
9
∆T-hot water
Parameter Setting
Full Name
Leaving water temperature for cooling (T1)
Leaving water temperature for heating (T2)
Room temperature for cooling (T3)
Room temperature for heating (T4)
Water tank Temperature (T5)
Room temperature control difference (∆t4)
Leaving water temperature difference for cooling (∆t1)
Leaving water temperature difference for cooling (∆t2)
Leaving water temperature difference for water heating (∆t3)
44
ELECTA-ECO
Range
Default
Remarks
7÷25°C
18°C
/
20÷60°C
45°C
/
18÷30°C
24°C
/
18÷30°C
20°C
/
40÷80°C
50°C
/
1÷5°C
2°C
/
2÷10°C
5°C
/
2÷10°C
10°C
/
2÷8°C
5°C
/