All parameters will be memorized upon power failure (see 2.6.1 On/Off memory).
No.
Item
1
Ctrl. state
2
2-Way valve
5
Solar setting
6
Water tank
7
Thermostat
Other
8
thermal
Optional
9
E-Heater
Remote
10
sensor
11
Air removal
12
Floor debug
Manual
13
defrost
14
Force mode
15
Tank heater
16
Gate-Ctrl.
17
Current
Limit
18
Address
19
Refri.
recovery
No
Display Name
1
T-HP max
2
Cool run time
3
Heat run time
2.5.1 Ctrl. state
This function allows to set the control on the supply water temperature
Remote air probe must be connected and configured, see 2.5.8 Remote Sensor ).
NOTE
When "Remote sensor" is set to "With", this setting can be set to "T-water out" or "T-room". When "Remote sensor" is set to "Without",
this setting can only be set to "T-water out".
All parameters will be memorized upon power failure (see 2.6.1 On/Off memory).
The default value is T-water out.
Commissioning Function Setting
Range
T-water out/T-room
Cool 2-Way valve, On/Off
Heat 2-Way valve, On/Off
With/Without
With/Without
Without/Air/Air+hot water
With/Without
Off/1/2
With/Without
On/Off
On/Off
On/Off
Off/Force-cool/Force-heat
Logic 1/Logic 2
On/Off
On/Off
[1÷125] [127÷253]
On/Off
Commissioning Parameters Setting
Full Name
Range
T-HP max
40÷55°C
Cool run time
1÷10min
Heat run time
1÷10min
Default
When "Remote sensor" is set to "With", it can
T-water out
It will decide the status of the 2-way valve under the
Off
"Cool" and "Cool + Hot water" modes.
It will decide the status of the 2-way valve under the
On
"Heat" and "Heat + Hot water" modes
Without
Without
This setting cannot be interchanged between "Air" and
Without
"Air+hot water" directly but via "Without" this option.
Without
Off
When it set to "Without", and the "Ctrl. state" will
Without
be defaulted to be "T-water out".
Off
Off
Off
Off
This setting is allowed when the water tank is
Logic 1
Off
Off
It ranges from 0 to 50A and the default is 16A.
1
Off
Default
50°C
3min [2-way valve Off]
5min [2-way valve On]
3min [2-way valve Off]
5min [2-way valve On]
"T-water out"
or on the room temperature
48
ELECTA-ECO
Description
be set to "T-room".
Function not available
/
/
/
/
/
/
/
available and the unit is OFF.
/
/
/
Remark
The unit, at the set point
reached, continues to work
for the time set here. The
higher the thermal inertia of
the system, the higher the
set time must be.
"T-room"
(in this latter case the