SMA Solar Technology AG
Parameters
Number of independent MPP
inputs /
strings per MPP input
Surge categories
Integrable DC surge arrester /
AC surge arrester
Efciency
Max. efciency
EU efciency
MPPT efciency, static
Enclosure
Dimensions (W / H / D)
Weight
Acoustic noise level
1)
at nominal grid voltage
2)
at nominal grid voltage, Cos(phi) = 1.
Parameters
Protection class (according
to IEC 62109-1)
Electrical
Electrical safety
Functional
Functional Safety
Installation Guide
SHP 75-10
1/1 (split up by external PV array
junction box)
AC: Surge category III
(SC III),
PV: Surge category II (SC II)
Type II / type II + III (combined)
98.8 %
98.2 %
99.9 %
740 × 570 × 306 mm
77 kg
58 dB(A) (typical)
SHP 75-10
I
• IEC 62109-1/IEC 62109-2
(Class I, grounded
Communication part Class II,
PELV)
• Voltage and frequency
monitoring
• Monitoring of DC current share
in AC current
• Insulation resistance monitoring
• FI monitoring
STP 60-10
1/1 (split up by external PV array
junction box)
AC: Surge category III
(SC III),
PV: Surge category II (SC II)
Type II / type II + III (combined)
98.8 %
98.3 %
99.9 %
740 × 570 × 306 mm
75 kg
58 dB(A) (typical)
STP 60-10
I
• IEC 62109-1/IEC 62109-2
(Class I, grounded
Communication part Class II,
PELV)
• Voltage and frequency
monitoring
• Monitoring of DC current share
in AC current
• Insulation resistance monitoring
• FI monitoring
SHP75-10-STP60-10-IA-xx-19
9 Technical Data
45