5 Installation
Figure 21: Installation area
Cable renuirements SHP 75-10
Figure 22: AC cable SHP 75-10
28
SHP75-10-STP60-10-IA-xx-19
Cable renuirements STP 60-10
Figure 23: AC cable SHP 60-10
Fuses and residual-current device (RCD)
For fuse and RCD information, refer to Section 9,
page 44. AC fuse rating must not exceed the
ampacity of the conductors used.
INFORMATION
Cables with multi-strand, fne-strand or extra
fne-strand conductors can be used for AC
connection. The cables must be suitable for a
temperature of at least 75°C.
When using fne-strand or extra f ne-strand
conductors, bootlace ferrules must be used for
the connection.
Figure 24: Cables with different conductors (from top to
bottom): multi-strand, fne-strand and extra
fne-strand
SMA Solar Technology AG
Installation Guide