Herunterladen Inhalt Inhalt Diese Seite drucken

Product And Functional Description - Dantherm 1.6 Serviceanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 40

Product and functional description

Il lustration
Illustration of the functional principle of the CDP 75/125 MKII/165:
Fresh air inlet
Air inlet
Functionality of the
The CDP 75 MK II, 125 MK II and 165 are working in accordance with t he condensation
d e humidifier
principle.
The humid air is drawn into the unit by a fan.
In the evaporator the air is cooled and when its temperature has fallen to below the dew
point, the water vapour condenses into droplets which are led to a drain.
The dry cold air is then passed through the condenser where it is reheated.
As a result of the released evaporator heat and the working energy of the compressor
being turned into heat energy, more heat is returned to the air than was previously ex-
tracted. This extra heat corresponds to an approximate increase in temperature of 5°C.
The repeated circulation of air through the unit reduces the relative humidity, giving
very rapid but gentle drying.
Condensate outlet
Connection of water-
cooled condenser
Cover panel
with fan
Control panel sec-
tion
Inspection door
Air outlet
Top cover panel
Reset of HP and ther-
mal relay
Front cover pa-
nel
Continued overleaf
23

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cdp 75125 mki165

Inhaltsverzeichnis