Herunterladen Diese Seite drucken

Technical Data - Siemens SITOP UPS500S Bedienungsanleitung

Grundmodul; kondensatormodul
Vorschau ausblenden Andere Handbücher für SITOP UPS500S:

Werbung

WARNINGS
Only properly qualified personnel may work on or around this equipment.
!
The successful and safe operation of this equipment is dependent on proper handling, storage and installation. Correct functioning is also
dependent on the use of SITOP ultra modules
CAUTION
Only trained personnel may open the unit. Electrostatically sensitive devices (ESD)
Description and Design
The DC-UPS module is a chassis unit in the SITOP power product range for mounting on a DIN rail of type DIN EN 50022-35x15/7.5.
The modules and the capacitor modules must be installed in accordance with the applicable DIN/VDE specifications or pertinent regulations in the country of
installation.
It buffers a proportion of the load current (max. 15A) of 24V load current supplies in the SITOP range.
Input "Input L+" on the DC-UPS module must be connected to output L+ of the 24V DC power supply unit and input "Input M" to output M of the power supply unit. It is
possible to connect max. 3 capacitor-modules via the connectors X10 and X30. The loads to be buffered are supplied via outputs "Output L+" and "Output M" on the
DC-UPS module with the voltage connected to the input. If the 24V DC supply voltage fails or drops below the set cut-in threshold, the capacitor module or the internal
capacitors are connected in to supply the loads.
The cut-in threshold, charging power and the buffering time can be set via DIP-switches. A switch is provided for setting a defined buffering (stored energy) time with
subsequent disconnection of the battery (see Settings), one switch for bridging the ON/OFF circuit, one switch for choosing if the output voltage is interrupted for 5 s
at the end of the buffering time or not.
The operating states of the DC-UPS module are signaled by four LEDs, two floating changeover and one normally-open contacts and a USB-interface (see
Signaling) and the control signal "Remote Timerstart".

Technical Data

Input quantities:
Rated input voltage:
Operating voltage range:
Max. input current at 24V and capacitor charging:
Max. input current at 24V and charged capacitors:
Power loss at 24V and capacitor charging:
Power loss at 24V and charged capacitors:
Charging time with low charging power and basic module -2EC41/-2EC51: appr. 110s /
220s
Charging time with high charging power and basic module -2EC41/-2EC51: appr. 55s / 120s
Charging time with low charging power and basic module -2EC41/-2EC51 and one capacitor
module: appr. 320s / 430s
Charging time with high charging power and basic module -2EC41/-2EC51 and one
capacitor module: appr. 160s / 220s
Settings
Setting the cut-in threshold:
If the input voltage drops below the selected cut-in threshold voltage, the UPS module switches over to floating operation. The loads are then supplied solely by the
UPS module. The cut-in threshold is set via three DIP-switches (see page 2 for position) according to table 1 (see page 7).
Setting range: 22.0 to 25.5V DC in 0.5-steps (delivery state: 22.5V DC ± 0.1V), accuracy ± 1.8%
Setting the charging current:
The capacitor module or the internal capacitors are charged via constant current until the set end-of-charge voltage is reached. Charging is then terminated. The
setting of the charging current determines how quickly the buffer ready state is restored after a discharging process. The charging current is set by a DIP switch
(position see page 2). Setting range: typ. 1A or typ. 2A (delivery state: 1A)
Setting the operating state ON/OFF:
Caution: For normal operation "ON" state is necessary (delivery state is "OFF"), in order to achieve that use DIP-switch closed or terminals X2.8 and X2.9
connected with X2.10
To prevent the capacitors from being discharged unintentionally (e.g. when the system power is disconnected), the DC-UPS module can be switched with a DIP-
switch (or a wire jumper (or floating connection) inserted between terminals X2.9 and X2.10) to operating state "OFF" (delivery state). In the "ON" state (DIP-switch
closed or terminals X2.8 and X2.9 connected with a floating normally-open contact (V
specification. In the "OFF" state, the module does not switch over to floating operation when the mains supply is disconnected but remains functional in every other
respect. If the module is switched to "OFF" in floating operation, it stops operating in floating mode.
During normal operation, the polling interval for the ON/OFF setting is appr. 20s.
Setting the buffering time:
The buffering time is set via five DIP-switches (see page 2 for position) as illustrated in Table 2 (see page 7) in 10s-steps from 5s to 315s. By switch 5 (delivery state
max. time) you can choose whether floating operation will be terminated after a prespecified period or when the exhaustive discharge threshold of the capacitors (=
maximum buffering time) is reached (delivery state: max. buffering time). Using the remote signal starts the timer to terminate after a prespecified period (switch 5 has
to be in position Off and switch interruption in position On). Once the battery has been disconnected, there is no way in which floating operation can be restarted
again by altering the switch setting. Only when the input voltage has recovered floating operation can be resumed. The buffering time is a appr. 3s with fully charged
capacitors and a load current of 15A.
Interruption of the output voltage:
By a DIP-switch you can choose if the output voltage is interrupted for 5 s at the end of the buffering time or not (delivery state : no interruption). Using the setting
"max. time" an interruption is started by the remote signal.
Protective and Monitoring Functions
Reverse polarity protection:
Overcurrent and short-circuit protection
and the internal static current limitation. Dynamic current limitation limits the output current to typ. 25A. Static dynamic limitation shuts down the output if currents are
greater than typ. 18A after about 110ms at short-circuit, and after about 200ms at overload. An internal (not accessible) 20A fuse protects the module in the event of a
fault. In normal operation automatic restart attempts are made approximately every 20s. In floating operation the module shuts down in store mode. Restart after
return to normal operation.
Siemens AG Österreich, 10/2008
24V DC
22 to 29V DC
17.5A DC
15.2A DC
appr. 11.0W
appr. 9.0W
UPS module is electronically protected against polarity reversal of the input voltage.
The
In normal operation and floating operation the UPS module is protected by the internal dynamic current limitation
:
Output quantities:
Rated output DC voltage:
Rated output direct current:
Output current range:
Output characteristic of charging regulator:
The capacitors are charged at an adjustable constant power until the
end-of-charge voltage is reached.
End-of-charge voltage: V = 21.8V DC
Charging current:
Buffering time at 15A load current with basic module -2EC41/-2EC51:
tp = 3s / 9s (typ.)
Buffering time at 15A load current with basic module -2EC41/-2EC51
and one add-on capacitor module: tp = 15s / 20s (typ.)
(see diagram 1 on page 7)
= 15V DC, I
= 10mA) ), the DC-UPS module is fully functional according to
max
max
5 von 8
English
VA1 = 24V DC
IA1 = 15A DC
IA1 = 0 ... 15A DC
P = 1 or 2A
SITOP UPS 500S
SITOP UPS 501S

Werbung

loading