Activating TEST mode
Press the heating buttons
mode. The boiler lights at the maximum heating power set as described in the following section.
The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash on the display; the heating power will be
displayed alongside.
To deactivate TEST mode, repeat the activation sequence.
In any case, TEST mode is disabled automatically after 15 minutes.
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 3.1).
Press the heating buttons
100).
Press the button
sec. 3.1).

3.2 Start-up

B
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any
leaks in connections.
Check correct prefilling of the expansion tank (ref. sec. 4.4).
Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the
air vent valve on the boiler and any vent valves on the system.
Fill the condensate trap and check correct connection of the condensate elimination system.
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
Check correct connection of the electrical system and efficiency of the earthing system
Make sure the gas pressure value for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler
EN
Downloaded from
www.Manualslib.com
(details 3 and 4 - fig. 1) at the same time for 5 seconds to activate the TEST
fig. 25 - TEST mode (heating power = 100%)
(details 3 and 4 - fig. 1) to increase or decrease the power (min. = 00 - max. =
(detail 8 - fig. 1) within 5 seconds; max. power will remain that just set. Exit TEST mode (see
reset
Checks to be made at first lighting, and after all maintenance operations that involved disconnection from the
systems or an operation on safety devices or parts of the boiler:
manuals search engine
eco
reset
comfort
cod. 3540M640 - 07/2008 (Rev. 00)