Connection with coaxial pipes
For coaxial connection, fit the unit with one of the following starting accessories. For the wall hole dimensions, refer to
sec. 4.1. Any horizontal sections of the fume exhaust must be kept sloping slightly towards the boiler, to prevent pos-
sible condensate from flowing back towards the outside and causing dripping.
Before proceeding with installation, check with table 2 that the maximum permissible length is not exceeded, bearing in
mind that every coaxial bend gives rise to the reduction indicated in the table. For example, a Ø 80/125 duct comprising
a 90° bend + 1 horizontal metre has a total equivalent length of 1.5 metres.
Table. 2 - Max. length coaxial ducts
Max. permissible length
Reduction factor 90° bend
Reduction factor 45° bend
EN
Downloaded from
www.Manualslib.com
fig. 20 - Examples of connection with coaxial pipes (
fig. 21 - Starting accessories for coaxial ducts 041007X0
cod. 3540M640 - 07/2008 (Rev. 00)
manuals search engine
= Air /
125
81
80
80
120
ENERGY TOP W 70
= Fumes)
Coaxial 80/125
4 m
0.5 m
0.25 m
17