7.1.5 Setting the ramp generator

The ramp generator determines the acceleration and deceleration time of the motor and can be
set within a range of 10 to 30 seconds by means of potentiometer R82. The ramp time setting
range can be adjusted by means of capacitor C71.
The ramp generator output can be connected to terminal X24:9 for slave drives.
Settings
R82
Potentiometer
R53
Resistor
R10
Resistor
C71
Capacitor
C4-C5
Jumper
C5-C6
Jumper
B4-B5
Jumper

7.1.6 Setting the limit monitor

The actual speed or actual current value can be monitored with the limit monitor. If the actual
current value exceeds or the actual speed value drops below the limit set by means of resistor
R2, then LED V98 / "GM" lights up and 0V are switched through to terminal X24:14 (open
collector output). The signal can be used, for example, as a "n=0" signal to activate a mechanical
holding brake.
Settings
R2
Resistor
A1-A2
Jumper
A5-A6
Jumper
A2-A3
Jumper
A4-A5
Jumper
Siemens AG ATD TD 6
Adjustment of ramp-up/ramp-down time (fine)
Adjustment of ramp-up/ramp-down time (coarse)
Minimum value: 10 kΩ
Fit if ramp-down time is required to be shorter than
ramp-up time
Minimum value: 10 kΩ
Defines ramp-up/ramp-down time range. 22µF ("as
supplied" value) corresponds to approx. 10s - 30s,
Increased capacitance of C71 extends ramp time.
Minimum value: 10 nF
Set jumper for operation with ramp-function generator,
Reference input 0...+10V via terminal X24.4
Set jumper for operation without ramp-function generator,
Reference input 0...-10V via terminal X24.4
Set jumper for ramp-function generator output at
terminal X24:9
Resonse threshold of limit monitor. Setting "as supplied":
5% of rated value (speed or current). Higher resistance
corresponds to higher response threshold.
Limit monitor checks current, if jumpers
A1-A2 and A5-A6 are set.
Limit monitor checks speed, if jumpers
A2-A3 and A4-A5 are set ("as supplied").
Operating Instructions 6RX1220-0DD74
6RA22
-8DD21-
- 55 -
June 1998