4.7 Applicable standards

VDE 0106, Part 100
Arrangement of operation elements in the vicinity of dangerous contact parts.
VDE 0110, Part 1
Isolation coordination for electrical equipment in low-voltage power systems.
Allowable degree of fouling 2 for modules and power section.
Only non-conductive fouling may occur. Condensation is excluded, since the components are
certified for humidity rating F.
EN 60204-1 (DIN EN 60204 part1 / VDE 0113 part1)
Electrical equipment of industrial machines
VDE 0160, Paragraphs 5.3.1.1.2 and 5.3.1.1.3
Regulations for equipment of power installations with electronic equipment
VDE 0298
Use of cables and insulated conductors in power installations
DIN IEC 38
Tolerance of the power supply voltage
EN 50081-2
Noise radiation
EN 50082-2
Noise immunity
DIN IEC 68
Mechanical stressing
IEC 68-2-6 for severity class 12

4.8 Fuses and reactors

The phase fuses specified are used to protect the power semiconductor devices. The commutating
reactors recommended guarantee conformance with VDE Specifications as regards to reaction on
the system, and can be matched to the relevant machine rating.
The machine manufacturer must be consulted before choosing the smoothing reactor required in
the armature circuit.
The printed-circuit board of the 5 and 12 A units is prepared for the retrofitting of fuse holders with
field fuses (F201, F202). If necessary, holders for 5 x 30 mm miniature fuses (500V) can be
soldered in. In this case, the R302 and R303 bridging resistances (0 ohms) must be removed.
Converters in special design 6RA22
resistances removed.
An F200 (0.1 A M) miniature fuse protects the line transformer in the unit.
Rated DC
current
5 A
5SD420 / 16 A
12 A
5SD420 / 16 A
22 A
3NE8015 / 25 A
40 A
3NE8017 / 50 A
Two phase fuses (and/or one fuse if there is a connection between L1 and N), a commutating
reactor and a smoothing reactor are required per unit.
Siemens AG ATD TD 6
-8DD21- -Z-A39 come with fuses F201, F202 fitted and
Phase fuses
Field fuses
(e.g. Wickmann No.19408)
1 A F / M
1 A F / M
Operating Instructions 6RX1220-0DD74
Commutating
reactors
4EM4700-0CB
4EM4900-5CB
-----
4EM5000-3CB
-----
4EM5107-7CB
6RA22
-8DD21-
- 43 -
June 1998