SIMOREG K
4.9 Special design G03 for field supply
The 6RA22
-8DD21-
shunt-wound motors. The standard models are not suitable for supplying severely fluctuating
inductive loads.
There is a special model (6RA22
windings. This is a 40 A unit specially modified for this application. "-Z-G03" is appended to the
Order No. (MLFB) to distinguish this unit from the standard models.
This model is operated as a pure converter. The speed controller is connected as a 1:1 inverting
amplifier. The field current reference is set with potentiometer "V". No external references or actual
values are required. The limit monitor is configured for monitoring the actual current. The maximum
DC current is approx. 37 A.
The following components have been modified compared to the standard model:
Ω
R2
47k
Ω
R17
82k
Ω
R18
180k
Ω
R97
10k
µ
C61
0.22
F
C349
22nF
The setting of the following plug-in jumpers is different from the standard setting:
A1 - A2
instead of
A5 - A6
instead of
B2 - B3
instead of
B8 - B9
instead of
C5 - C6
instead of
C8 - C9
instead of
D1 - D2
instead of
in addition to the changes above, terminals X24.13 and X24.17 are interconnected.
It is recommended that an overvoltage protection device, consisting of a varistor and a capacitor,
be connected on the DC side to protect the converter against overvoltages in the event of a power
failure.
The varistor should be rated to suit the energy content of the load inductance (W = 0.5 x L x I
Capacitor: approx. 56nF / 1000V.
For applications with a smaller demand of field current I
available:
MINIREG F10
MINIREG F33
- 44 -
June 1998
range converters are designed for supplying the armature circuits of DC
-8DD21- -Z-G03) available for supplying such loads as field
instead of
10 k
instead of
90k
instead of
18k
instead of
100k
µ
instead of
1.0
instead of
not fitted
A2 - A3
A4 - A5
B1 - B2
B7 - B8
C4 - C5
C7 - C8
D2 - D3
I
= 10A
Order No.
MAX
I
= 22A
Order No.
MAX
Operating Instructions 6RX1220-0DD74
Ω
Response threshold of the limit monitor
Ω
Adaptation of actual current value
Ω
Current controller feedback
Ω
Reference poti "V" action
Current controller feedback
F
Length of firing pulses
, purpose-designed field supplies are
MAX
6RA8222-8PA0
6DM1001-0WB00-2
6RA22
-8DD21-
2
Siemens AG ATD TD 6
).