Ex-relevante technische Daten
7.2.2

IECEx Issue No. 3

IECEx
Certificate No.:
Issue No.:
Typ:
Standards:
Type and marking
Temperature Class
Electrical data for type TZIDC-110 with marking Ex ia IIC T6 resp. Ex ib IIC T6
Input circuit
(terminals +11, -12 resp.+, -)
Voltage
Current
Power
Characteristic
line
Local interface for
communication (LKS) and
programming interface (X5)
44
Ex ia IIC resp. Ex ib IIC
T4
T5
T6
In type of protection "Intrinsic Safety" (Ex ia IIC resp. Ex ib IIC)
only for the connection to a certified intrinsically safe circuit (e.g.
FISCO power supply) with the following maximum values
according to the following table:
FISCO power supply
ia/ib for group IIB/IIC
U
= 17.5 V
i
l
= 380 mA
i
P
= 5.32 W
i
For the connection to a programmer resp. a PC outside of the
explosive hazardous area only.
TZIDC, TZIDC-110, TZIDC-120
Ex ia IIC T6
Ex nA II T6
Ex nL IIC T6
IECEx TUN 04.0015X
3
Intrinsic safety "i", Type of protection "n"
IEC 60079-0:2000
IEC 60079-11:1999
IEC 60079-15:2001
IEC 60079-27:2005-04
TZIDC-110
Ambient temperature range
-40 ... 85 °C
-40 ... 55 °C
-40 ... 40 °C
Barriere or power supply
ia/ib for group IIB/IIC
U
= 24 V
i
l
= 250 mA
i
P
= 1.2 W
i
linear
TZIDC-110
Ex nA IIC resp. Ex nL IIC
-40 ... 85 °C
-40 ... 65 °C
-40 ... 50 °C
CI/TZIDC/110/120-DE