Installing and connecting the equipment
Store the packaging for later use.
■
Switch off the system and secure so it cannot be turned on by
■
unauthorised persons.
Drain the pipes.
■
Make sure the system's pipework is clean.
■
Equipment with a closing spring may be mounted in any installation
position. Equipment without a closing spring may only be installed
in vertical pipes with an upward direction of flow.
Make sure the equipment is free from foreign bodies.
■
Make sure the direction arrow on the body is pointing in the
■
desired direction of flow.
Install and centre the equipment between the flanges with two
■
seals. See diagrams.
Rotate the equipment with a spiral centring device (1) or centring
■
cam (2) until the centring device is in contact with all screws.
Equipment with a body centring device (3) does not have to be
rotated.
EN