Safety Time Control Device

17.3 Timing diagram SCB-04-01 with Configuration Pr24

Table 12 shows the corresponding extract from the configuration table.
Configuration No.
Auto
Man.
reset
reset
Table 12: Extract from Configuration table SCB-04-01 - Configuration Pr24
Legend : F3: AUX C1 inverted signal for non-time-delayed safe outputs/contacts
F4: AUX C2 inverted signal for time-delayed safe outputs/contacts
Figure 26 shows the timing diagram for Configuration Pr24.
Figure 26: Timing diagram for SCB-04-01 with Configuration Pr24 (Qualitative representation)
t
:
Activation of the power supply. The C1 and C2 are activated as soon as the device is ready for operation
1
t
:
Safety circuit I11/I12 is closed. Outputs/contacts are not yet switched
2
t
:
Pressing the reset button at X1
3
t
:
All safe outputs/contacts are activated with the falling edge of the reset button and the AUX switches off
4
t
:
Requirement of the safety function by opening the safety circuit I11/I12
5
t
:
Outputs O1, O2 switches off immediately (reaction time). C1 switch on
6
t
:
Safety circuit I11/I12 is closed again before the delay time has elapsed
7
t
:
Without pressing the reset button at X1, O1 and O2 are reactivated and C1 switch off. The current delay time
8
for 17-8 / 27-28 is stopped and reset. Relay contacts 17-18/27-28 stays activated
t
:
Request for safety function by opening safety circuit I11/I12
9
t
: Outputs O1, O2 switches off immediately (reaction time). C1 switch on
10
t
: After the parameterized delay time has elapsed, the relay contacts 17-18/27-28 switch off and C2 switch on
11
t
: Safety circuit I11/I12 is closed. Outputs/contacts are not yet switched
12
t
: Pressing the reset button at X1
13
t
: With the falling edge of the reset button, O1, O2 and 17-18/27-28 switch on and C1 and C2 switch off
14
t
: Power supply is switched off. All outputs and relay contacts switch off immediately
15
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Deutschland • Tel +49 241 9105010
Fax +49 241 91050138 • info@zander-aachen.de • www.zander-aachen.de
Non-delayed
outputs/contacts
Man. reset
with autom.
O1
O2
17/18
re-triggering
24
Delayed
outputs/contacts
27/28
O1
O2
17/18
27/28
AUX Function
Delay type
C1
C2
F3
F4
Off-delay
33