Safety Time Control Device
ATTENTION!
•
Make sure that the supply voltage of the device is safely applied during loading the new
configuration. A power-off during the loading process leads to a non-acknowledgeable
error condition. In this case, the device must be returned to the manufacturer
•
If the starting behaviour "automatic reset" is selected and the safety circuit closed, the
SCB will be activated immediately
13.2 Parametrization of a delay time
After a configuration has been successfully loaded via the PUK, the desired delay time
can be parameterised. The parametrization of the delay time is protected against external
adjustment by PIN 4 - 2.
After successful entry, the delay time can be set via the push/rotary button and the dis-
play, depending on the time variant, in the range between 0.1 and 99 s/min/h with a reso-
lution of ≥ 0.1 s/min/h as shown in Figure 20.
1.
Enter (2s)
Y1
Y1
1. Operating state
The parametrise menu is entered by pressing the push/rotary button for 2 s.
INFO: PIN request can be entered only in safe state. Open the safety circuit and wait until
all safety outputs/contacts have switched off.